技术参数
避雷器使用场所 |
型号 |
系统标称电压有效值 kV |
避雷器额定电压有效值 kV |
避雷器持续运行电压有效值 kV |
直流1mA参考电压 ≥ kV |
标称放电电流5kA |
通流容量 |
|||
陡坡冲击电流残压 峰值≤kV |
雷电冲击电流残压 峰值≤kV |
操作冲击电流残压 峰值≤ kV |
2ms方波冲击电流≥A |
4/10us大电流冲击≥kA |
||||||
低压型 |
HY1.5W-0.28/1.3 |
0.22 |
0.28 |
0.24 |
0.60 |
- |
1.3 |
- |
50 |
10 |
HY1.5W-0.5/2.6 |
0.38 |
0.50 |
0.42 |
1.20 |
- |
2.6 |
- |
50 |
10 |
|
HY1.5W-0.58/3.2 |
0.48 |
0.58 |
0.46 |
1.4 |
- |
3.2 |
- |
75 |
35 |
|
HY1.5W-0.62/3.6 |
0.52 |
0.62 |
0.5 |
1.6 |
- |
3.6 |
- |
75 |
35 |
|
HY1.5W-0.8/3.9 |
0.66 |
0.8 |
0.68 |
1.8 |
- |
3.9 |
- |
75 |
35 |
|
HY1.5W-0.9/4.3 |
0.69 |
0.9 |
0.72 |
1.9 |
- |
4.3 |
- |
75 |
35 |
|
配电型 |
HY5WS-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
HY5WS-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 |
|
HY5WS-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 |
|
线路型 |
HY5WX-5/15 |
3 |
5 |
4.0 |
8.0 |
19.6 |
15.0 |
14.5 |
100 |
65 |
HY5WX-10/30 |
6 |
10 |
8.0 |
15.0 |
34.5 |
30.0 |
25.5 |
100 |
65 |
|
HY5WX-17/50 |
10 |
17 |
13.6 |
25.0 |
57.5 |
50.0 |
42.5 |
100 |
65 |
|
HY5WX51/134 |
35 |
51 |
40.8 |
73.0 |
154.0 |
134.0 |
114.0 |
600/800 |
65 |
|
电 |
HY5WZ-5/13.5 |
3 |
5 |
4.0 |
7.5 |
15.5 |
13.5 |
11.5 |
200 |
65 |
HY5WZ-10/27 |
6 |
10 |
8.0 |
14.4 |
31.0 |
27.0 |
23.0 |
200 |
65 |
|
HY5WZ-17/45 |
10 |
17 |
13.6 |
24.0 |
51.8 |
45.0 |
38.3 |
200 |
65 |
|
HY5WZ-26/66 |
20 |
26 |
20.8 |
37.0 |
76.0 |
66.0 |
56.0 |
400 |
65 |
|
HY5WZ-34/85 |
20 |
34 |
27.2 |
48.0 |
75.0 |
85.0 |
95.0 |
400 |
65 |
|
HY5WZ-34/95 |
20 |
34 |
27.0 |
52.0 |
84.0 |
95.0 |
106.0 |
400 |
65 |
|
HY5WZ-51/134 |
35 |
51 |
40.8 |
73.0 |
154.0 |
134.0 |
114.0 |
600/800 |
65 |
|
发 |
HY5WD-4/9.5 |
3.15* |
4 |
3.2 |
5.7 |
10.7 |
9.5 |
7.6 |
400 |
65 |
HY5WD-8/18.7 |
6.3* |
8 |
6.3 |
11.3 |
21.0 |
18.7 |
15.0 |
400 |
65 |
|
HY5WD-13.5/31 |
10.5* |
13.5 |
10.5 |
18.6 |
34.7 |
31.0 |
25.0 |
400 |
65 |
|
HY5WD-17.5/40 |
13.8* |
17.5 |
13.8 |
24.4 |
44.8 |
40.0 |
32.0 |
400 |
65 |
|
电 |
HY2.5WD-4/9.5 |
3.15* |
4 |
3.2 |
5.7 |
10.7 |
9.5 |
7.6 |
200 |
65 |
HY2.5WD-8/18.7 |
6.3* |
8 |
6.3 |
11.3 |
21.0 |
18.7 |
15.0 |
200 |
65 |
|
HY2.5WD-13.5/31 |
10.5* |
13.5 |
10.5 |
18.6 |
34.7 |
31.0 |
25.0 |
200 |
65 |
|
电机中性点型 |
HY1.5W-2.4/6 |
3.15* |
2.4 |
1.9 |
3.4 |
- |
6.0 |
5.0 |
200 |
65 |
HY1.5W-4.8/12 |
6.3* |
4.8 |
3.8 |
6.8 |
- |
12.0 |
1.0 |
200 |
65 |
|
HY1.5W-8/19 |
10.5* |
8 |
6.4 |
11.4 |
- |
19.0 |
15.9 |
200 |
65 |
|
HY1.5W-10.5/23 |
13.8* |
10.5 |
8.4 |
14.9 |
- |
23.0 |
19.2 |
200 |
65 |
|
HY1.5W-12/26 |
15.75* |
12 |
9.6 |
17.0 |
- |
26.0 |
21.6 |
200 |
65 |
|
HY1.5W-13.7/29.2 |
18.0* |
13.7 |
11.0 |
19.5 |
- |
29.2 |
24.3 |
200 |
65 |
|
HY1.5W-15.2/31.7 |
20.0* |
15.2 |
12.2 |
21.6 |
- |
31.7 |
26.4 |
200 |
65 |
|
电 |
HY5WR-10/27 |
6 |
10 |
8 |
14.4 |
- |
27.0 |
21.0 |
400 |
65 |
HY5WR-17/46 |
10 |
17 |
13.6 |
24.0 |
- |
46.0 |
35.0 |
400 |
65 |
|
HY5WR-51/134 |
35 |
51 |
40.8 |
73.0 |
- |
134.0 |
105.0 |
600/800 |
65 |
|
变压器中性点 |
HY1.5W-30/80 |
35 |
30 |
24 |
44.0 |
- |
80 |
76 |
600/800 |
65 |
HY1.5W-33/90 |
35 |
33 |
26.4 |
48.0 |
- |
90 |
86 |
600/800 |
65 |
|
HY1.5W-42/102 |
35 |
42 |
33.6 |
60.0 |
- |
102 |
95 |
600/800 |
65 |
|
电气化铁道型 |
HY10WT-42/120 |
27.5 |
42 |
34.0 |
66 |
138 |
120 |
98 |
600/800 |
100 |
注:"*"表示电机额定电压有效值。 |
型号说明
本品依据GB11032-2010《交流无间隙金属氧化物避雷器》,以HY5WS-17/50为例对其型号说明如下:
Y:金属氧化物避雷器;
H:复合外套,无H即为瓷套;
5:标称放电电流,因电压等级而异;
W:无间隙,C:串联间隙,B:并联间隙;
S:配电型,Z:电站型,D:电机型,R:电容型,T:铁道型:
17:避雷器额定电压(kV),即允许加在避雷器上的最大允许工频电压有效值,因型号和电压等级而异。
50:标称放电电流下最大残压峰值(kV),因型号和电压等级而异。
使用条件
1)环境温度:-40℃~+60℃;
2)海拔高度:小于2000m(高于2000m请选用高原型产品);
3)额定频率:48Hz~62Hz;
4)最大风速不得超过35m/s;
5)地震裂度7度及以下地区;
试验项目
1)直流1mA参考电压:在避雷器两端施加直流电压,待流过避雷器的电流稳定于1mA后,读出的电压数值,该值不得小于技术参数表中的规定值。
2)泄漏电流:在避雷器的两端施加0.75倍直流1mA参考电压,此时流过避雷器的泄漏电流不大于50微安;
3)不得对本产品进行工频放电电压试验。
金属氧化物避雷器
产品介绍/特点:
1、优异的保护特性
金属氧化物避雷器核心部件氧化锌电阻片具有十分优良的非线性伏安特性,在正常工作电压下仅有几百微安的电流通过,当过电压侵入时,避雷器迅速动作,流过电阻片的电流迅速增大,避雷器两端的电压保持在避雷器的残压下,限制了过电压的幅值,释放了过电压的能量,从而保护了设备。动作后氧化锌电阻片又恢复高阻状态,使电力系统正常工作。
2、大的通流能力
金属氧化物避雷器的通流能力表示避雷器具有吸收各种雷电过电压、操作过电压,工频暂态过电压能量的能力。
本公司生产的金属氧化物避雷器的通流能力完全符合甚至高于国家标准的要求。4/10μs大电流冲击耐受、2ms方波通流能力、线路放电等级、能量吸收能力等指标均达到了国内领先水平。
3、工频耐受能力
电力系统中由于各种原因,如单相接地、长线电容效应以及甩负荷等,会引起工频电压的升高或产生幅值较高的暂态过电压,而此避雷器具有在一定时间内承受一定程度工频电压升高的能力,这就是避雷器的工频过电压耐受时间特性。
4.良好的耐污秽性能
我公司现在批量生产的避雷器所用外套的最小爬电比距为:
Ⅱ级 中等污秽地区:爬电比距20mm/kV
Ⅲ级 重污秽地区:爬电比距25mm/kV
Ⅳ级 特重污秽地区:爬电比距31mm/kV
5.独特的压力释放装置
35kV及以上等级的金属氧化物避雷器带有压力释放装置。压力释放装置能及时排除内部故障压力。
6.高的运行可靠性
金属氧化物避雷器长期运行的可靠性取决于产品的质量,也同选型是否合理有关。
下列三个方面对产品质量有重要影响
氧化锌电阻片的伏安特征及耐老化特征;
避雷器元件的密封性能;
避雷器整体结构的合理性。
我公司产品使用的的氧化锌电阻片,均已按国家标准的规定通过了115℃、1000h、荷电率为85%~95%的老化试验,试验结果证明其耐老化性能非常优良。
7.良好的密封性能
避雷器元件采用气密性好、老化性能优良的优质橡胶作为密封材料,采用控制密封圈压缩量和增涂密封胶等措施,确保产品密封可靠。在避雷器元件内部充以微正压高纯干燥氮气(氮气纯度达99.9999%)使避雷器产品的性能稳、定运行安全可靠。
密封试验采用多种方法互补,每台产品经过车间、品管部门两级部门、多道工序把关,避雷器产品的漏气率采用氦质谱检漏仪检测,漏气率不大于4.43×10-7Pa.L/s,确保不合格的产品不流入用户端。
8.机械性能
避雷器的机械性能主要考虑三个方面因素;
避雷器的顶端承受导线的最大允许拉力;
作用于避雷器上的最大风力;
承受的地震力。
我公司避雷器所用的瓷外套及复合外套均通过设计和试验验证,机械性能完全符合并优于国标规定的使用要求。